DN20MD30/35 3-Way Adjustable Temperature Mixing Valve
The WINNING® adjustable 3-way thermostatic mixing valve automatically blends hot and cold water to maintain a stable outlet temperature, with adjustable ranges of 30–70°C or 35–65°C.
Description
Product Overview
The WINNING® adjustable 3-way thermostatic mixing valve uses a self-actuated thermostatic element to automatically blend hot and cold fluids in response to the mixed outlet temperature. By continuously modulating the two inlet flows, the valve maintains the selected outlet temperature within its control range without requiring electricity or an external controller.
This upgraded DN20 model is designed for mixing applications only.
The standard valve features a brass body with G3/4″ (DN20) connections. Two adjustable temperature ranges are available: 30–70°C and 35–65°C. Other temperature ranges can be supplied for OEM requirements upon request.
The valve is suitable for fluid-based systems with operating temperatures up to 95°C, subject to fluid compatibility and the specified pressure limits.
Key Advantages
- Adjustable outlet temperature
- Two standard adjustment ranges: 30–70°C and 35–65°C
- Self-actuated thermostatic control—no electricity or external controller required
- Brass body with a responsive thermostatic element
- Narrow control band and stable temperature regulation
- Compact, low-mass construction for fast response
- Responds to fluid temperature rather than system pressure
- Custom temperature ranges and OEM configurations available
Design Features
- Three-port construction for thermostatic mixing
- Proportional blending of hot and cold inlet flows
- Continuously adjustable temperature setting
- Automatic response to changes in inlet temperature and demand
- Compact design for integration into residential, commercial, and industrial systems
- Mixing-only configuration prevents confusion with diverting valve applications
Typical Applications
- Solar water-heating systems
- Air source heat pump water-heating systems
- Solar or heat pump systems combined with auxiliary heaters
- Domestic and commercial hot-water temperature control
- Constant-temperature baths
- Washbasins, sinks, and washdown systems
- Loop-type hot-water circulation systems
- Boiler and heating-system temperature regulation
- Heat-exchanger temperature control
- Radiator and hydronic heating systems
- Hydraulic-fluid cooling systems
- Lube-oil cooling control
- Make-up water temperature control
- Electric equipment cooling
- Air-conditioning and process-fluid systems
- Water-conservation systems requiring controlled mixed-water temperatures
Operation
The WINNING® adjustable 3-way thermostatic mixing valve has two inlet ports and one mixed outlet port:
- Hot inlet: receives fluid from the hot-water or heated-fluid source.
- Cold inlet: receives cold water, return fluid, or another lower-temperature fluid.
- Mixed outlet: delivers fluid at the selected temperature.
The required outlet temperature is selected within the valve’s specified adjustment range.
When the mixed outlet temperature is below the selected setting, the thermostatic element increases the proportion of hot inlet flow and reduces the proportion of cold inlet flow. As the mixed outlet temperature rises toward the selected setting, the valve progressively reduces the hot flow and increases the cold flow.
The valve continuously modulates both inlet flows to compensate for normal changes in inlet temperature and flow demand. It operates automatically and requires no electrical power.
Solar or Heat Pump Water Heating with Auxiliary Heating
In solar or heat pump water-heating systems, the valve can be installed downstream of the available hot-water source to control the final delivery temperature.
When the hot-water inlet temperature is higher than the selected outlet temperature, the valve automatically blends the hot water with cold water to produce the required mixed-water temperature.
When the hot-water inlet temperature is lower than the selected outlet temperature, the valve cannot increase the water temperature by itself. The solar- or heat-pump-heated water must first be raised to the required temperature by an auxiliary heat source, such as an electric water heater or boiler. The valve then blends the heated water with cold water to maintain the selected outlet temperature.
| Item | Specification |
|---|---|
| Product Type | Adjustable 3-Way Thermostatic Mixing Valve |
| Model | DN20 adjustable mixing model — final model code to be confirmed |
| Port Size | G3/4″ (DN20) |
| Brand | WINNING® |
| Function | Mixing |
| Body Material | Brass |
| Adjustable Temperature Range | 30–70°C or 35–65°C |
| Custom Temperature Range | Available upon request |
| Temperature Accuracy | ±2°C |
| Maximum Operating Temperature | 95°C |
| Maximum Operating Pressure | 1.0 MPa |
| Flow Coefficient | Cv 1.5 |
| Net Weight | 300 g |
| Power Requirement | Self-actuated thermostatic operation |
Notes
- Other adjustment ranges are available upon request.
- Unless otherwise specified, the temperature-control accuracy is ±2°C under rated operating conditions.
- The selected outlet temperature must be lower than the available hot-inlet temperature. The valve cannot heat the fluid.
- For diverting or flow-switching applications involving this valve, please consult the manufacturer.
- Install the valve according to the port markings on the valve body.
- Confirm fluid compatibility, system pressure, temperature conditions, and required flow capacity before installation.
Only logged in customers who have purchased this product may leave a review.